100 Ton Portable Air Cooled Chiller

 


Unit Performance / Data

100 Ton Portable Air Cooled Chiller Package

General

Manufacturer Custom Air Products & Services, Inc.
Unit Model Number PCHH-100TC-0NN0NN-5E5-0-P
Price Call for quote
Filter Requirements N/A

Chiller Dimensions

Length (Cage) 200″ (16’8″)
Length (Base) 204 1/2″ (17’0.5″)
Width 101 1/2″ (8’5.5″)
Height 102″ (8’6″)
Unit Weight 11,000 lbs.
 

Electrical

Certification UL Listed equipment and components
Single Point Power Supply 460V / 3PH / 60HZ
Connections 1 @ Series 16 Male per conductor
Min. Circuit Ampacity (MCA) 244 (MCA must be used for circuit sizing-includes pump)
Max. Overcurrent Protection (MOCP) 250
 

Evaporator Flow

Water Volume, Gals. 51
Max Water Side Pressure, PSIG 150
Max Refrigerant Side Pressure, PSIG 450
Min Chilled Water Flow Rate, GPM 100
Max Chilled Water Flow Rate, GPM 385

 

For more information contact:
713-460-9009

Unit Drawings / Photos

Plan View with Dimensional Data

 

Plan View with Dimensional Data

Integrated 300 GPM Pump with Bypass and Dimensional Data

 

Integrated 300 GPM Pump with Bypass and Dimensional Data


Main Pump Panel and 4" Chilled Water Connections

 

Main Pump Panel and 4″ Chilled Water Connections

 

Lifting/Stacking Structural Skid & Cage with Dimensional Data

 

Lifting/Stacking Structural Skid & Cage with Dimensional Data

 

Integrated 300 GPM Pump With Bypass

 

Integrated 300 GPM Pump With Bypass