30 Ton Portable Air Cooled Chiller


Unit Performance / Data

30 Ton Portable Air Cooled Chiller Package

General

CAT Class TBD
Manufacturer Custom Air Products & Services, Inc.
Unit Model Number PCHH-30TC-0NN0NN-5E5-0-PG2CEUP
Price Call for quote
Filter Requirements N/A

Chiller Dimensions

Length (Cage) 178″ (14′-10″)
Length (Base) 184″ (15′-4″)
Width 55″ (4′-7″)
Height 65″ (5′-5″)
Est. Unit Weight 4,550 lbs.
 

Estimated Electrical

Certification UL Listed equipment and components
Single Point Power Supply 460V / 3PH / 60HZ
Connections 1 @ Series 16 Male per conductor
Min. Circuit Ampacity (MCA) 90 (MCA must be used for circuit sizing-includes pump)
Max. Overcurrent Protection (MOCP) 100
 

Estimated Evaporator Flow

Water Volume, Gals. 3.2
Max Water Side Pressure, PSIG 150
Max Refrigerant Side Pressure, PSIG 650
Min Chilled Water Flow Rate, GPM 30
Max Chilled Water Flow Rate, GPM 150

 

For more information contact:
713-460-9009

Unit Drawings / Photos

Plan View with Dimensional Data

Plan View with Dimensional Data


Lifting/Stacking Structural Skid & Cage

Lifting/Stacking Structural Skid & Cage

Chiller Control Panel View

Chiller Control Panel View

Product Data

Chiller Features

  • York YCAL0033EE46XEB air cooled chiller
  • TEAO condenser fan motors
  • Direct drive suction gas cooled, hermetic, scroll compressors
  • Brazed plate heat-exchanger
  • Super quiet design
  • High efficiency/performance
  • R410A refrigerant
  • Freeze protection to -20F with 3/4″ foam insulated evaporator & protective aluminum jacketing, and refrigerant
    isolation valves (discharge valve)
  • Suitable for high ambient operation up to 125F with high ambient option
  • Suitable for low ambient operation down to 0F with low ambient option
  • Enhanced capacity control with hot gas bypass option
  • Dual circuit machine for staging and efficiency
  • Louvered condenser coil guards
  • Standalone York DDC temperature controls
  • ETL / cETL listed to US and Canadian safety standard
  • ASHRAE 90.1 compliance
  • ARI Standard 550/590
  • ANSI/NFPA Standard 70

Package Features

  • Phase monitor and phase fail indicator light (red)
  • Main power on indicator light (green)
  • Master On/Off switch
  • One hour compressor crank case heater lock out timer
  • Common trouble alarm terminal
  • Integrated main power wiring with Cam-Lock electrical connections and associated wiring
  • Single point 460V/3PH/60HZ power application power connection for Chiller/Pump package
  • Additional differential pressure safety switch for chiller protection
  • EnergyGuard condenser coil corrosion protection
  • Temperature and pressure gauges (Inlet & Outlet)
  • Chiller provided with hydronic isolation and drain valves.
  • Hot dip galvanized certified structural lifting/stacking skid and integrated tie-downs
  • 4″ Dixon type quick connect fittings (Inlet & Outlet)
  • 4″ Butterfly Valve for system balancing on Outlet
  • Chilled water temperature and pressure indication (Inlet & Outlet)
  • Integrated 100 GPM @ 100′ TDH system pump with bypass for local or remote pump application

30 Ton Portable Air Cooled Chiller Package - Unit Performance/Data

30 Ton Portable Air Cooled Chiller Package – Unit Performance/Data

Pump Performance

Motor 7.5 HP
Motor Type TEFC
Configuration Vertical In-Line
Variable Speed N/A
Gallon per Min. 100
Total Discharge Head 100′

Graph

Equipment specifications are based on manufacturer’s published data; capacity may vary based upon field conditions

For more information contact:
713-460-9009