40 Ton Compact HVAC


Unit Performance / Data

40 and 65 Ton Compact Hybrid HVAC Units

General

CAT/CLASS TBD
Manufacturer Custom Air Products & Services, Inc.
Unit Model Number PPKH-40TD-0NN120KE-5E5-P2-VS1CEUP
Price Call for quote
Duct Connections 3×20″ Supply Air & 6×20″ Return Air
 

Electrical

Single Point Power Supply 460V / 3PH / 60HZ
Connections 4 Cam-Lok connectors
 
Cooling MCA 111
Cooling MOCP 150
 
Heating MCA with 117kW 174
Heating MOCP with 117kW 200
 
Dehumidification MCA 263
Dehumidification MOCP 300

Dimensions

Length (Base) 134″ (11’2″)
Width 84″ (7′)
Height 101″ (8’5″)
Est. Unit Weight 7,300 lbs.

Fan Performance

CFM TSP MOTOR HP
14000 4.25 15

Heating

kW STAGES VOLTAGE
117 3 460/3/60

Filter

SIZE EFF. TYPE
(12) 20″ x 20″ x 2″ 30% Pleated

For more information contact:
713-460-9009

Unit Drawings / Photos

Plan View with Dimensional Data

Plan View with Dimensional Data

Three Supply Air Connections with Dimensional Data

Three Supply Air Connections with Dimensional Data


Control Panel with Dimensional Data

Control Panel with Dimensional Data

Six Return Air Connections with Dimensional Data

Six Return Air Connections with Dimensional Data

Product Data

Compact Hybrid HVAC Unit Features

  • Two stages of refrigeration capacity control
  • Four stages of heating capacity control
  • Dual independent refrigerant circuits utilizing scroll compressors
  • Electrical heat (117kW)
  • 14,000 CFM static constant volume fan rated at 4.25 TSP
  • VFD air volume control
  • Direct drive condenser fans
  • Environmentally safe 410A refrigerant
  • Stainless steel condensate pan – connection size 1″ FPT
  • Easy access panels for efficient serviceability
  • Heavy duty skid with dual forklift slots
  • Coated Lifting / Stacking cage
  • Rugged design built for rental duty
  • Corrosion resistant condenser coil guards
  • 1″ Cabinet insulation
  • Three 20″ supply air connections with duct friction locks and covers
  • Six 20″ return air connections with duct friction locks and covers

Compact Hybrid HVAC Unit Functions

  • Single point 460V/3PH/60HZ power application power connection utilizing four Cam-Lock power cables
  • Panel mounted high voltage disconnect
  • Main power on indicator light (green)
  • Phase monitor and phase fail indicator light (red)
  • Heating status and cooling status lights (blue)
  • Master On/Off switch lights (amber)
  • Low ambient condenser fan cycling switch
  • Hour meters for each refrigerant circuit
  • DDC compressor protection module
  • Common trouble alarm terminal
  • High and low pressure safety switches
  • Air flow differential pressure safety switch
  • Heater safety control circuit and limits
  • Micro processer temperature controller
  • DH operation utilizing a single enable control switch
  • Two stage thermostat

Unit Performance / Data

Operation Performance

40 Ton Compact Hybrid HVAC Unit - Unit Performance/Data

Fan Performance

Motor 15 HP
Motor Type TEFC
Drive Configuration Belt
Belt Size TBD

Cooling Coil Performance

CFM FPM EDB/EWB LDB/LWB MBH
Total
MBH
Sens.
ROW/FIN REFG. SUCT.
TEMP
SUPER
HEAT
14,000 504.9 79.8 / 66.5 54.8 / 54.4 504.7 363.3 6 / 9 410A 45.0 20.0

Compressor Performance

MBH
TOTAL
CAPACITY
SUPER
HEAT
SUB-
COOLING
AMBIENT
AIR OVER
COND
TEMP
EVAP
TEMP
RETURN
GAS TEMP
LIQUID
LINE
TEMP
DISCHARGE
TEMP
REFG.
510.0 20.0 15.0 95.0 125.0 45.0 65.0 110.0 198.0 410A

Equipment specifications are based on manufacturer’s published data; capacity may vary based upon field conditions

For more information contact:
713-460-9009