40 Ton Compact Vertical Pkg Unit


Unit Performance / Data

40 Ton Compact Vertical Package Unit

General

Manufacturer Custom Air Products & Services, Inc.
Unit Model Number PPKH-40TD-0NN90KE-5F6-P2-G2UP
Price Call for quote
Duct Connections 3×20″ Supply Air & 6×20″ Return Air
 

Electrical

Single Point Power Supply 460V / 3PH / 60HZ
Connections 4 Cam-Lok connectors
 
Cooling MCA 101
Cooling MOCP 125
 
Heating MCA with 90kW 141
Heating MOCP with 90kW 150
 
Dehumidification MCA 218
Dehumidification MOCP 225

Dimensions

Length (Base) 96″ (8′)
Width 72″ (6′)
Height 101″ (8’5″)
Unit Weight 5,000 lbs.

Fan Performance

CFM TSP MOTOR HP
13500 4.25 15

Heating

kW STAGES VOLTAGE
90 3 460/3/60

Filter

SIZE EFF. TYPE
(6) 24″ x 30″ x 2″ 30% Pleated

For more information contact:
713-460-9009

Unit Drawings / Photos

Control Panel

Control Panel

Six Return Air Connections

Six Return Air Connections


Access Panels View with Dimensional Data

Access Panels View with Dimensional Data

Plan View with Dimensional Data

Plan View with Dimensional Data

For more information contact:
713-460-9009

 

40 Ton Vertical Package Unit Features

  • Three stages of heating capacity control
  • Dual independent refrigerant circuits utilizing scroll compressors
  • Electrical heat (90 kW)
  • 13,500 CFM high static constant volume fan rated at 4.25 TSP
  • 15 HP, 1725 RPM motor, TEFC
  • Direct drive condenser fans
  • Environmentally safe 410A refrigerant
  • Stainless steel condensate pan – connection size 1″ FPT
  • Easy access panels for efficient serviceability
  • Heavy duty skid with dual forklift slots
  • Rugged design built for rental duty
  • Corrosion resistant condenser coil guards
  • 1″ Cabinet insulation
  • Three 20″ supply air connections with duct friction locks and covers
  • Six 20″ return air connections with duct friction locks and covers

40 Ton Vertical Package Unit Functions

  • Single point 460V / 3PH / 60HZ power application power connection utilizing four Cam-Locks power cables
  • Panel mounted high voltage circuit breaker
  • Main power on indicator light (green)
  • Phase monitor and phase fail indicator light (red)
  • Heating status and cooling status lights (blue)
  • Master On / Off switch lights (amber)
  • Low ambient condenser fan cycling switch
  • Hour meters for each refrigerant circuit
  • DDC compressor protection module
  • High and low pressure safety switches
  • Air flow differential pressure safety switch
  • Heater safety control circuit and limits
  • Two stage thermostat

 

Unit Performance / Data

Fan Performance

Motor 15 HP
Motor Type TEFC
Drive Configuration Belt
Belt Size TBD

Operation Performance

Operational performance

Cooling Coil Performance

CFM FPM EDB/EWB LDB/LWB MBH
Total
MBH
Sens.
ROW/FIN REFG. SUCT.
TEMP
SUPER
HEAT
13,500 492.9 80.0 / 67.0 56.4 / 55.9 476.1 343.8 4 / 15 410A 45.0 20.0

Compressor Performance (Model #ZP236KCE-TED)

MBH
TOTAL
CAPACITY
SUPER
HEAT
SUB-
COOLING
AMBIENT
AIR OVER
COND
TEMP
EVAP
TEMP
RETURN
GAS TEMP
LIQUID
LINE
TEMP
DISCHARGE
TEMP
REFG.
476.0 20.0 15.0 95.0 130.0 45.0 65.0 114.8 199.0 410a

Equipment specifications are based on manufacturer’s published data; capacity may vary based upon field conditions.

For more information contact:
713-460-9009