80 Ton High Static AC NEMA 4 & 7


Unit Performance / Data

80 Ton High Static AC Unit NEMA 4 and 7

General

Manufacturer Custom Air Products & Services, Inc.
Unit Model Number (NEMA 4) PPKH-80TD-0NN0NN-5E5-P2-S1CEUP
Unit Model Number (NEMA 7) PPKH-80TD-0NN0NN-5B2-P2-S1CEUP
Price Call for quote
Duct Connections 3×20″ Supply Air & Louvered Return Air Grille
 

Electrical

Single Point Power Supply 460V / 3PH / 60HZ
Connections 4 Cam-Lok connectors
 
Cooling MCA 166
Cooling MOCP 200

Dimensions

Length 216″ (18′)
Width 82″ (6’10”)
Height 100 1/4″ (8’4.25″)
Unit Weight (N4) 9,800 lbs.
Unit Weight (N7) 10,250 lbs.

Fan Performance

CFM TSP MOTOR HP
10000 6 15

Filter

SIZE EFF. TYPE
(4) 24″ x 24″ x 2″ 30% Pleated

For more information contact:
713-460-9009

Unit Drawings / Photos

Control Panel & Louvered Returned Air Grille - NEMA 4

Control Panel & Louvered Returned Air Grille – NEMA 4

Control Panel & Louvered Returned Air Grille - NEMA 7

Control Panel & Louvered Returned Air Grille – NEMA 7

Plan View - NEMA 4 & 7

Plan View – NEMA 4 & 7

Plan View - NEMA 4

Plan View – NEMA 4

End View - NEMA 7

End View – NEMA 7

For more information contact:
713-460-9009

 

Air Conditioning Unit Features

  • 10,000 CFM high static plenum fan rated at 6 TSP
  • 100% outside with three 20″ supply duct connections (Option: four 20″ return air duct connections)
  • Two stages of refrigeration capacity control
  • Dual independent refrigerant circuits
  • Dual circuit hot gas bypass
  • Direct drive condenser fans
  • Environmentally safe 410A refrigerant
  • Stainless steel condensate pan
  • Dual condensate connections (size 1 1/4″ FPT)
  • Easy access panels for efficient serviceability
  • Isolated high / low voltage control panels
  • Double wall evaporator cabinet construction
  • Heavy duty skid, forklift slots, tie-downs with coated lifting / stacking cage (Option: stack and cage to be hot dipped galvanized)
  • Rugged design built for rental duty
  • Corrosion resistant condenser coil guards
  • Custom coatings / colors

Air Conditioning Unit Functions

  • NEMA 4 to meet General Purpose Electrical Classification
  • NEMA 7 model is suitable for explosion hazardous classification to meet Class 1, Division 2, Group C & D, T3
  • Single point 460V / 3PH / 60HZ power application power connection utilizing four Cam-Lock power cables
  • Panel mounted high voltage disconnect
  • Main power on indicator light (green)
  • Phase monitor and phase fail indicator light (red)
  • Circuit #1 and #2 cooling failure alarm light (red)
  • Master On / Off switch
  • Low ambient fan cycling control
  • High static evaporator fan
  • Hour meters for each refrigerant circuit
  • DDC compressor protection module
  • Common trouble alarm terminal
  • High and low pressure safety switches
  • Micro processer temperature controller
  • Entering and leaving air control capability
  • Refrigerant isolation valves, sight glasses, and filter driers

 

Unit Performance / Data

Operation Performance

Operational performance

Cooling Coil Performance

CFM FPM EDB/EWB LDB/LWB MBH
Total
MBH
Sens.
ROW/FIN REFG. SUCT.
TEMP
SUPER
HEAT
10,000 440 95.0 / 80.0 53.1 / 52.8 978.2 454.9 8 / 14 410A 45.0 20.0

Equipment specifications are based on manufacturer’s published data; capacity may vary based upon field conditions.

For more information contact:
713-460-9009