100% Pre-Treatment Outside Air Handling Unit

100% Pre-Treatment Outside Air Handling Unit

Does the “new normal” have you rethinking how to modify your outside air handling equipment to meet higher ventilation or filtration requirements?

Custom Air Products has a solution to fit your unique air handling requirements. We have four options below designed and engineered to assist you with solving this task.

Contact us for more details.

Air handling unit
Model CAPS-AHU 23K CAPS-AHU 17K CAPS-AHU 11K CAPS-AHU 5K
Configuration Horizontal Draw Through Horizontal Draw Through Horizontal Draw Through Horizontal Draw Through
Dimensions (inches) 192 L x 120 W x 94 H 192 L x 109 W x 88 H 192 L x 82 W x 82 H 192 L x 69 W x 60 H
Total Airflow (CFM) 23,000 17,000 11,000 5,000
External Static (IN.WG.) 3.0 3.0 3.0 3.0
Total Static 5.5 5.5 5.5 5.5
Fan Type Plenum Fan Array Plenum Fan Array Plenum Fan Array Plenum Fan Array
Fan Modulation EC Motor Direct Drive EC Motor Direct Drive EC Motor Direct Drive EC Motor Direct Drive
Quantity of Fans 4 3 2 2
Motor Watts (each) 5700 5700 5700 5700
FLA Motor Amps (total) 36 27 18 18
Volts/Phase/Hertz 460/3/60 460/3/60 460/3/60 460/3/60
Heating Hot Water Hot Water Hot Water Hot Water
Total MBH 884 588 355 255
Face Velocity 450 450 450 450
EAT °F / LAT °F 28 / 55 28 / 55 28 / 55 28 / 55
EWT °F / LWT °F 120 / 100 120 / 100 120 / 100 120 / 100
Flow (gpm) 71 58 35 18
Cooling Coil Chilled Water Chilled Water Chilled Water Chilled Water
Total MBH 2,235 1,397 941 620
Sensible MBH 932 789 530 300
Face Velocity 450 450 450 450
EAT DB °F / LAT WB °F 90 / 80 95 / 77 95 / 77 95 / 77
LAT DB °F / LAT WB °F 55 / 54 55 / 54 55 / 54 55 / 54
EWT °F / LWT °F 44 / 60 44 / 60 44 / 60 44 / 60
Flow (gpm) 274 153 103 80
Fliter Section MERV 8 + MERV 11 MERV 8 + MERV 11 MERV 4 + MERV 11 MERV 8 + MERV 11

Equipment specifications are based on manufacturer’s published data; capacity may vary based upon field conditions.

Perspective View

Plan View

Features

  • “Best in class” footprint configuration
  • Long-lasting all aluminum construction
  • True thermal break double wall construction
  • Ultraviolet germicidal irradiation
  • Filtration (multistage)
  • Energy saving ECM Fan
  • IAQ stainless steel drain pan
  • AHRI certified coils
  • Stainless steel coil casing
  • High-performance access doors
  • Vapor tight LED service lights
  • Additional options available

ECM Fan Grid

Energy Saving ECM Fans

Filter & Coil Section with UVGI

Ultraviolet Germicidal Irradiation (UVGI)

For more information contact Custom Air Products & Services: by email or phone 713-460-9009.

We are ready to serve you

24 / 7 HVAC Service

713-460-9009